Analysis Duration of Potential Difference Neutralizer for Substation Grounding System

Main Article Content

Riza Arif Pratama
Hermawan
Mochammad Facta

Keywords

Abstract

The grounding system design of the 150 kV substation have resolve affect in lightning strike area. The purpose of this study is to determine the duration of the potential difference penetration that occurs due to direct or indirect lightning strikes. The parameter method grounding system uses a combination of  R and L for the grid section and a combination of RLC for the rod section. Simulations due to direct lightning strikes in nearby areas greatly affect the spike in the amount of potential difference. The potential difference in the area closest to the lightning strike with a maximum surge of 57.42 V with a neutralization duration of 0.21 μs. At the furthest distance from a lightning strike, the maximum potential difference spike is only 3.14 V with a neutralization duration of 2 μs. The average duration of neutralization due to lightning strikes is 2 μs. In the simulation of a direct lightning strike striking electrical equipment, it causes a very high potential difference spike in lightning strike area of ​​992.96 V with a spike duration of 0.012 μs. The farthest area point at the location of the lightning strike has a spike of 31.07 V with a spike duration of 0.06 μs. The duration of neutralization at a potential difference below 1 V, has a duration of more than 2 μs depending on the distance from the location of lightning strike. The grounding system design is able to perform good performance with a fast potential difference neutralization duration in the event of a direct or indirect lightning strike. Lightning strikes that occur will not cause dangerous step and touch voltages for personnel in the 150 kV substation area.

References

H. N. Amadi, “Design of Grounding System for A . C . Substations with critical consideraion of the Mesh, Touch and Step Potentials,” European Journal of Engineering and Technology, vol. 5, no. 4, pp. 44–57, 2017.

R. A. Pratama, Hermawan, and M. Facta, “Analysis of Grounding System in 150 kV Kudus Substation,” 2018 5th International Conference on Information Technology, Computer, and Electrical Engineering (ICITACEE), pp. 245–250, 2018.

D. Prasad and H. C. Sharma, “Design of Grounding System for High Voltage Substations,” no. 6, pp. 61–65, 2013.

P. R. Bonda and M. K. Mishra, “Optimized Design of Earthing System for Substations with High Soil Resistivity and Limited Plot Area,” in 2018 20th National Power Systems Conference (NPSC), 2018, pp. 1–6. doi: 10.1109/NPSC.2018.8771780.

R. Shariatinasab and J. Gholinezhad, “The effect of grounding system modeling on lightning-related studies of transmission lines,” Journal of Applied Research and Technology, vol. 15, pp. 545–554, 2017.

S. J. Varghese, “Practical Approach on Lightning and Grounding Protection System,” International Journal of Engineering Research, vol. 4, no. 4, pp. 192–196, 2015, doi: 10.17950/ijer/v4s4/406.

S. N. Nikolovski, Z. Baus, and G. Knežević, “Frequency and time response of power plant grounding system exposed to lightning strike,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 512–525, 2016, doi: 10.11591/ijece.v6i2.9356.

M. Purba, P. N. Medan, A. Purba, and P. N. Medan, “the Effect of Conductive Cement As an Grounding Media of,” no. April 2020, pp. 0–9, 2019.

B. S. Nasional, “Persyaratan Umum Instalasi Listrik 2000 (PUIL 2000),” DirJen Ketenagalistrikan, vol. 2000, no. Puil, pp. 1–133, 2000.

M. Nazih, “Safety assessment of high voltage substation earthing systems with synthetic geotextile membrane,” Journal of Mechatronics, Electrical Power, and Vehicular Technology, vol. 10, no. 2, pp. 85–91, 2019, doi: 10.14203/j.mev.2019.v10.85-91.

Hermansyah, “Evaluasi Kehandalan Sistem Grounding Pada Instalasi Listrik Rumah Tinggal Di Kabupaten Bantaeng,” Jurnal Ilmiah d’Computare Volume 9 Edisi Juli 2019 EVALUASI, vol. 9, p. 5, 2019.

R. Tonape, Susmita Baburao;Pujari, Komal; Vhanmare, “Research Design of Grounding System for Substation, Using Soil Enhancement Material,” International Journal of Advanced Engineering, Management and Science, vol. 7, no. 2, pp. 49–54, 2021, doi: 10.22161/ijaems.72.6.

N. Permal, M. Osman, M. Z. A. Ab. Kadir, and A. M. Ariffin, “Review of Substation Grounding System Behavior Under High Frequency and Transient Faults in Uniform Soil,” IEEE Access, vol. 8, pp. 142468–142482, 2020.

Z. Liu, W. Shi, and B. Zhang, “Numerical analysis of transient performance of grounding grid with lightning rod installed on multi-grounded frame,” Energies (Basel), vol. 14, no. 12, pp. 1–13, 2021, doi: 10.3390/en14123392.

M. Fakhraei, M. Mahmoudian, and E. M. G. Rodrigues, “Grounding system modeling and evaluation using integrated circuit based fast relaxed vector fitting approach, considering soil ionization,” Applied Sciences (Switzerland), vol. 10, no. 16, 2020, doi: 10.3390/app10165632.

S. G. Farkoush et al., “Investigation and optimization of grounding grid based on lightning response by using ATP-EMTP and genetic algorithm,” Complexity, 2018, doi: 10.1155/2018/8261413.

M. Adnan, Z. Abdul-Malek, N. S. M. Din, M. I. Jambak, Z. Nawawi, and M. A. B. Sidik, “Effects of lightning impulse front time on substation grounding system performance,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 20, no. 2, pp. 569–574, 2020, doi: 10.11591/ijeecs.v20.i2.pp569-574.

D. Almanda and A. I. Ramadhan, “Design Optimization of Distance Grid and Ground Rod in the Earth System,” Journal of Applied Science and Advanced Technology, pp. 53–58, 2019.

F. Murdiya, F. Febrizal, C. Stevany, H. A. Sano, and F. Firdaus, “The effect of lightning impulse characteristics and line arrester to the lightning protection performance on 150 kV overhead lines: ATP-EMTP computational approach,” Journal of Mechatronics, Electrical Power, and Vehicular Technology, vol. 10, no. 2, pp. 49–59, 2019, doi: 10.14203/j.mev.2019.v10.49-59.

N. Mungkung, S. Wongcharoen, T. Tanitteerapan, C. Saejao, and D. Arunyasot, “Analysis of Lightning Surge Condition Effect on Surge Arrester in Electrical Power System by using ATP / EMTP Program,” Proceedings of World Academy of Science, Engineering and Technology, no. September, pp. 297–301, 2007.

Y. Cai, H. Ji, D. Wang, X. Lei, Y. Sun, and S. Yuan, “Optimal construction method and demonstration application of multi-in-one station grounding system,” Global Energy Interconnection, vol. 4, no. 5, pp. 520–530, 2021, doi: 10.1016/j.gloei.2021.11.005.