Pengaruh Pemasangan Static Var Compensator pada Sistem Transmisi Tenaga Listrik (Studi Kasus: Sistem Transmisi Tenaga Listrik 150 Kv Sumbagut)

Main Article Content

Syiska Yana
Zulkarnaen Pane
Sandro Levi Panggabean

Keywords

Abstract

This paper discussed about the influence of Static VAR Compensator (SVC) in transmission system 150 kV, Sumbagut region. Transmission system and SVC parameters in this study is simulated by using computer. Purpose of simulation was to show voltage profile of the system before and after installed SVC. Based on simulation for the condition before installed SVC, there were four Buses; Aek Kanopan, Kuala Tanjung, Kisaran and Rantau Prapat which have critical voltages sequentially 89,92%; 89,92%; 89,97%; and 89,96%. After installed SVC, voltage profile of the busses increased sequentially 91,7%; 91,74%; 91,7%; dan 91,73%. Based on simulation result, SVC improved voltage profiles in transmission system.   

Keywords : Static Var Compensator, Voltage, Transmission


Abstrak—Studi ini membahas tentang pengaruh pemasangan Static VAR Compensator (SVC) pada sistem transmisi tenaga listrik 150 kV Sumbagut. Metode yang digunakan dalam studi ini adalah simulasi menggunakan komputer dan perhitungan untuk mendapatkan parameter-parameter SVC yang akan disimulasikan. Simulasi dilakukan untuk melihat profil tegangan pada sistem sebelum dan sesudah dipasang SVC. Dari hasil simulasi sebelum pemasangan SVC diperoleh data Bus yang memiliki tegangan kritis atau dibawah standar. Bus yang mengalami tegangan yang dibawah standar atau kritis adalah Bus Aek Kanopan, Kuala Tanjung, Kisaran dan Rantau Parapat. Besar tegangan masing-masing Bus berturut-turut 89,92%; 89,92%; 89,97%; dan 89,96%. Setelah pemasangan SVC nilai tegangan pada Bus berubah menjadi 91,7%; 91,74%; 91,7%; dan 91,73%. Dari hasil simulasi dapat dilihat bahwa pemasangan SVC berdampak pada perbaikan profil tegangan sistem  transmisi.

Kata Kunci : Static Var Compensator, Tegangan, Transmisi


References

[1] Padiyar, K.R., FACTS Controller in Transmission and Distribution, New Age International (P) Limited Publisher (2007).
[2] Sastry Verdam, R., Mulukutla S. Sarma, Power Quality: VAR Compensation in Power Systems, CRC Press (2009).
[3] Hirdesh Chaturvedi, Paramjeet Kaur, Power Quality Enhancement using Different “FACTS” Devices, International Journal of Engineering Research and Development Vol. 10, pp. 51-57 (2014).
[4] Mohan Matur, R., Rajiv K Varma, Thyristor-Based Facts Controllers for Electrical Transmission Systems, John Wiley & Sons, Inc. (2002).
[5] Ramlal Das, D. K. Tanti, Transient Stability of 11-Bus System Using SVC and Improvement of Voltage Profile In Transmission Line Using Series Compensator, American Journal of Electrical Power and Energy Systems, pp. 76-85, (2014)
[6] John J. Paserba, How FACTS Controllers Benefit AC Transmission Systems, Mitsubishi Electric Power Products
[7] S.RaviKumar, B.Ramoji Rao, D.Ramesh, The Study of Voltage Profile and Power Quality with SVC in Transmission System at Different Loads , International Journal of Engineering Research and Applications, Vol.3, pp. 543-549 (2013).
[8] Guneet Kour, G. S. Brar, Jaswanti Dhiman, Improvement by Voltage Profile by Static Var Compensators in Distribution Substation, International Journal of Instrumentation Science pp: 21-24, (2012)
[9] Tarlochan Kaur, Sandeep Kakran, Transient Stability Improvement of Long Transmission Line System by Using SVC, International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering, Vol. 1, pp. 218-227, (2012).