Impact of Transformer Grounding On TRV During Inductive Load Switching at Transmission and Substation Service Unit (ULTG) Maros

##plugins.themes.bootstrap3.article.main##

Muhammad Khaidir
Sriwati
Saktiani Karim
Faridah
Fadhli Rahman
Syarifuddin Baco

Keywords

Transformer Grounding, Transient Recovery Voltage, Circuit Breaker

Abstract

This paper investigates the impact of transformer grounding configurations on Transient Recovery Voltage (TRV) during fault current interruption in high-voltage power systems. The study evaluates three grounding schemes: Solid–Solid, Solid–Floating, and Solid–Resistance, applied on a step-down transformer located at the Tello substation. Each configuration was modeled and simulated using ETAP 19 software to observe TRV behavior under three-phase fault conditions. The results demonstrate significant variations in TRV profiles depending on the grounding type. The Solid–Solid configuration exhibits the highest TRV peak (22,500 V) and the steepest Rate of Rise of Recovery Voltage (RRRV), reaching 833.33 kV/ms, indicating severe stress on circuit breaker insulation. In contrast, the Solid–Floating configuration yields a moderate TRV peak (19,800 V) with less consistent waveform stability due to the absence of a defined secondary reference. Meanwhile, the Solid–Resistance scheme, using a 20 Ω resistor, produces the most damped TRV waveform with the lowest peak (17,100 V) and RRRV (approximately 589.66 kV/ms), offering improved insulation coordination. The comparative analysis confirms that controlled grounding through resistance effectively mitigates TRV magnitude and oscillation, making it a viable approach to enhance circuit breaker performance and reliability. These findings can be used to guide grounding system design in high-voltage substations to reduce the risk of re-ignition or insulation failure.

References

M. W. N. Ahsan, “Evaluasi Sistem Pentanahan pada Transformator Daya,” Block Caving – A Viable Alternative?, vol. 21, no. 1, pp. 1–9, 2021. [Online]. Available: https://doi.org/10.1016/j.solener.2019.02.027

Y. A. M. Ambabunga, H. Masiku, and E. A. M. Sampetoding, “Karakteristik Transformator 3 Fasa (Hubung Bintang dan Delta) pada Sistem Tenaga Listrik AC,” Journal Dynamic Saint, vol. 6, no. 1, pp. 12–18, 2021. [Online]. Available: https://doi.org/10.47178/dynamicsaint.v6i1.1195

D. Ajiatmo, Transmisi dan Distribusi Tenaga Listrik, 2023.

A. Bintari, U. Mudjiono, and A. T. Nugraha, “Analisa Pentahanan Netral dengan Tahan Menggunakan Sistem TN-C,” Elektriese: Jurnal Sains dan Teknologi Elektro, vol. 12, no. 02, pp. 92–108, 2022. [Online]. Available: https://doi.org/10.47709/elektriese.v12i02.1853

D. R. Damara, “Pengaruh Konfigurasi Belitan Transformator Daya Tiga-Fasa terhadap Feroresonansi pada Sistem Jaringan Distribusi,” 2017.

A. A. D. I. K. Febrianti, “Analisis Sistem Proteksi Arus Lebih pada Penyulang Cendana Gardu Induk Bungaran,” Jurnal Ampere, p. 2, 2019.

Y. P. Ferdani, “Studi Pemasangan Generator Circuit Breaker di PLTU Pacitan dengan Mempertimbangkan Transient Recovery Voltage (TRV),” 2019.

J. Jamaaluddin, I. Anshory, I. Sulistiyowati, and A. Ahfas, Buku Ajar Pengantar Teknik Tenaga Listrik. UMSIDA Press, 2022. [Online]. Available: https://doi.org/10.21070/2022/978-623-464-054-0

A. A. Pratomo, L. Patras, and H. Tumaliang, “Analisa Perancangan Gardu Induk 150 kV di Kabupaten Muna,” 2022.

Y. P. Putra, “Analisis Transient Recovery Voltage pada Switching Circuit Breaker Tegangan Menengah Menggunakan Gelombang Berjalan dengan Variasi Hubungan Belitan Trafo Daya,” 2020.

G. M. Saroinsong, L. S. Patras, and N. M. Tulung, “Analysis Performance Circuit Breaker SF6 70kV at Sawangan Switchyard,” pp. 1–6, 2021.

F. D. C. Utomo, “Daya Tegangan Tinggi terhadap Transient Recovery Voltage Akibat Switching Beban,” 2020.

S. Yusniati, E. S. Nasution, and R. I. Pangestu, “Analisis Kinerja Circuit Breaker pada Sisi 150 kV Gardu Induk Lamhotma,” Semnastek UISU, pp. 77–82, 2019.

IEEE Power & Energy Society, “IEEE Standard for High-Voltage AC Circuit Breakers,” IEEE Std C37.04–2018, 2018.

IEEE Power & Energy Society, “IEEE Guide for the Application of High-Voltage Circuit Breakers,” IEEE Std C37.010–2011, 2011.

IEC, IEC 62271-100: High-voltage switchgear and controlgear – Part 100: Alternating-current circuit-breakers, International Electrotechnical Commission, 2012.

C. R. Paul, Analysis of Multiconductor Transmission Lines, 2nd ed., Wiley-IEEE Press, 2007.

A. Greenwood, Electrical Transients in Power Systems, 2nd ed., Wiley-Interscience, 1991.

R. Rudenberg, Transient Performance of Electric Power Systems, McGraw-Hill, 1950.

J. J. Grainger and W. D. Stevenson, Power System Analysis, McGraw-Hill, 1994.

M. H. J. Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions, IEEE Press, 2000.

D. Mukherjee and A. Chakrabarti, Power System Protection and Switchgear, McGraw-Hill Education, 2010.

S. A. Soman, S. A. Khaparde, and S. A. Kale, Computational Methods for Large Sparse Power Systems Analysis: An Object Oriented Approach, Springer, 2002.